Power-supply system in a 19" case, 1800 W
- Input voltage 100V to 256V AC
- One to three source modules with 600W each and with active load sharing
- Two to five independent protected output circuits
- One to two input circuits for connecting of backup batteries
- Battery management including LVD
- A fully digital control unit with a communication module
- Allows remote administration via HTTP and SNMP
- Local reporting of selected alarms by means of potential free contacts
- Efficiency 92%
- Meets the requirements of the standards EN 60950, EN 55022/B
- Operation modes:
- parallel mode,
- redundant mode
- Indication of operating state of the source module on the front panel
- It is possible to attach a module that enables connecting two independent input networks (input redundance)
Source module - Output
- Output voltage 48V (adjustable and controlled in the range of 48 – 54.5V)
- Performance reduction 2%/°C (from 40 to 50°C)
- Output power: max. 1800 W
- Operating state indication: output voltage U A (green)
- Output voltage deviation at:
- Variation of supply voltage max. 0.1% 100 ... 253 V AC
- Static load change max. 1 % share 10 – 90 % load
- Current limit
- Typ. trigger value 12,2 A fixed
- Typ. hold up time 20 ms at 230 V AC, I out=100%, Vout=80%Vnom
- Circuit-closing and time-current characteristic without a back-swing, approximately a monotonous flow
- Efficiency NSD-1800-480 typ. 92 % / 1800 W at 230 V ACin, 100% working load
Source module - Input
- Input voltage 100 - 253 V AC
- Input frequency 47 – 63 Hz
- Input power max. 6 A at 230 V
- Interference elimination class EN 55 022/B 150 kHz... 30 Mhz
- Circuit-closing wave max. 6 A at cold start
- Internal input fuse 5x20 mm F6,3AH/250 V in each power supply unit
Remote control and signalling
- A detailed description can be obtained on request at bke@bke.cz
Electromagnetic compatibility
- Interference emission, EN 55 022 class B
- Interference immunity according to the EN 50082-1
electrostatic discharge, EN 61000-4-2 8 kV contact discharge (Level 4)
- Group of pulses resistance (burst) 2 kV, 5/50, 5 kHz, EN 6100-4-5
- Surge impulse EN 61-000-4-5
- 4 kV (cl. 4) asym.: L,N against PE, machine in operation
- 2 kV (cl. 4) sym.: L against N, machine in operation
Electric safety
- Test voltage 3 kV AC input/output
- 1.5 kV AC in/PE
- 500 V AC out/PE
- Air distance / surface way 6.0 mm in/out
- Class I VDE 0106 part 1, IEC 536
- Earth wire resistance < 0.1 Ohm. VDE 0805
- Protection IP 20 DIN 40 050, IEC 529
Operating data
- Operating temperature max. 0° to +50°C
- optimum temperature +18 - +25 °C
- Storage temperature -20 to +70 °C
- Air humidity max. 90% RH
- Cooling by means of natural convection – do not hinder passage of cooling air
- Altitude up to 2000 m above the sea level
Distribution
The output voltage circuits, just as the circuits for accumulator connection, have electronic protection against short-circuit in form of DC circuit breakers. Distribution may include up to 4 output circuits and 2 accumulator circuits. The accumulator circuit contains also protection against low voltage discharge (LVD). The state of all circuits is monitored by a control unit.
Operating position
The machine is designed to be mounted into and operate in a 19" rack.
Dimensions and weight
19" power-supply system with a touch cover – intended to be mounted into devices 3HE mounting height (132mm), 84 TE mounting width (425mm), depth 300mm Weight: approx. 9 kg (a fully equipped system)
5 years warranty (since production year 2009)
|